DESIGN GUIDE
COLD STORES
VESDA
VESDAVESDA
VESDA
®
ASPIRATING SMOKE DETECTION
2
VESDA
®
August, 2001
DESIGN GUIDE
© Vision Fire & Security. All Rights Reserved.
DISCLAIMER
This publication is a guide only. Reference to local codes and standards for compliance of system
design should always be sought. No part of this document may be reproduced or transmitted in any
form or by any means, electronic or mechanical, including photocopying and recording, for any
purpose without the express written permission of Vision Systems. For more information, please
contact your nearest Vision Fire & Security office.
Cold Stores
3
1
.
2
.
3
.
3
.
1
.
3
.
2
.
3
.
2
.
1
.
3
.
3
.
3
.
4
.
3
.
4
.
1
.
3
.
4
.
2
.
3
.
5
.
3
.
6
4
.
0
®
Cold Stores
DESIGN GUIDE
August, 2001
© Vision Fire & Security. All Rights Reserved.
CONTENTS
INTRODUCTION..........................................................................................................4
DESIGN CONSIDERATIONS.......................................................................................5
LEVEL OF PROTECTION............................................................................................6
PERFORMANCE-BASED DESIGN..............................................................................7
ROOM PROTECTION..................................................................................................7
Sampling Point Location..........................................................................................8
Along Underside of Ceiling........................................................................................9
CONDENSATION CONSIDERATIONS......................................................................12
External Condensation...........................................................................................12
Internal Condensation............................................................................................12
IN-RACK PROTECTION ............................................................................................14
VOID PROTECTION...................................................................................................14
GLOSSARY ...............................................................................................................15
VESDA
4
1
.
VESDA
®
August, 2001
DESIGN GUIDE
© Vision Fire & Security. All Rights Reserved.
INTRODUCTION
Refrigerated warehouses and cold storage facilities are temperature controlled environments that
contain a wide range of inventory such as fresh and frozen foods, pharmaceuticals and pre-packaged
product lines.
The ultra dry environment, and highly combustible nature of the insulation and
packaging materials present a significant fire risk in these facilities. Reliable, very early smoke
detection systems can assist in protecting these facilities and the associated stock assets from the
threat of fire.
As an innovative pioneer of aspirating technology, VESDA provides the earliest possible warning of a
potential fire by detecting the incipient (pre-combustion) stage of a fire event. This guide has been
developed by VESDA engineers who have extensive design and installation knowledge in cold
storage environments.
The Cold Store Design Guide is intended as a reference for consultants and designers involved in the
specification of refrigerated storage facilities. It discusses relevant design considerations and
recommendations regarding the installation of an aspirating smoke detection system in cold storage
environments.
Cold Stores
5
2
.
®
Cold Stores
DESIGN GUIDE
August, 2001
© Vision Fire & Security. All Rights Reserved.
DESIGN CONSIDERATIONS
The following aspects should be considered during the specification and design of an aspirating
system:
••
•
•
••
•
•
Temperature ranges of the cold store and associated rooms;
Airflow characteristics of the room;
••
•
•
Defrost cycles and associated condensation;
••
•
•
Product flammability and toxicity risks; and
• • Penetrations in the ceiling insulation. VESDA 6 3 . 1 . 1 * VESDA ® August, 2001 DESIGN GUIDE © Vision Fire & Security. All Rights Reserved. LEVEL OF PROTECTION Cold storage environments exhibit harsh climatic conditions. Their operating temperatures typically range between 8°C to –40°C (46°F to –40°F) resulting in extremely dry atmospheres. Key cold store risks include: a) ignition hazards from electrical and mechanical faults from conveyor/transport equipment, b) lighting or hot spots caused by maintenance operations, and c) the fuel hazards from the highly combustible nature of polystyrene and polyurethane foams, wooden pallets and plastic wrapping. The low humidity levels of cold stores further exacerbate the heat release rate of burning materials. High-bay storage racking can also affect the airflow and impede the detection and response to a fire event. The extreme temperatures of refrigerated storage facilities are a primary challenge to detecting a cold store fire as most forms of detection are not designed to operate in harsh climatic environments. High airflows created by blast chiller units and condensation (ice formation within the facility) can impede the operation of conventional “passive” detectors. Internationally recognised fire standards further state, that unless specified, smoke detectors should not be installed if the operating temperature is below 0°C (NFPA 72 ). Although water supression i.e. sprinklers, may be used in warehouse applications, they may be ineffective in cold storage environments. In the event of a fire, the activation of water can create environmental and occupational hazards such as ice formation (black ice*). The release of water can also generate large amounts of dense fog, causing reduced visibility and impeding an appropriate fire brigade response. To minimise damage and loss in cold stores, a fire must be detected at a very early stage. VESDA’s reliable, very early warning minimises the likelihood of product loss (either from fire and/or contamination), facility damage and operational downtime. The following guidelines are to assist consultants and designers to achieve the optimum level of protection required by a cold store facility. Internationally recognised fire standards and codes of practice or requirements should always be taken into consideration. The spacing or density of the sampling holes are dictated by local standards. Sensitivity levels are determined by the application environment and the level of response to specific tests and will not be addressed in this guide. Table 1 shows the possible areas of protection of a cold store environment. Areas Required ✔✔ ✔ ✔ Recommended Optional Freezers/Chillers Plant/Maintenance Areas ✔✔ ✔ ✔ Return Air Path Protection ✔✔ ✔ ✔ Ante-Rooms/Loading Bays ✔✔✔✔ ✔ ✔ ✔ ✔ Racking Protection ✔✔ ✔ ✔ Ceiling Void ✔✔ ✔ ✔ Table 1 Areas of Protection The following sections will describe design recommendations related to the different protection areas.All pipework designs should be verified using the VESDA Sampling Pipe Modelling Program – TM
ASPIRE This program illustrates the significance of various parameters in an aspirating smoke detection system so that the most appropriate design can be applied. NFPA 72 National Fire Alarm Code, 1999. A thin layer of ice, which forms on concrete due to sprinkler activation. Cold Stores 7 3 . 1 . 3.2. 1) 2) ® Cold Stores DESIGN GUIDE August, 2001 © Vision Fire & Security. All Rights Reserved. PERFORMANCE-BASED DESIGN Performance-Based design determines the best fire protection system by assessing the environmental risks at the concept design stage. VESDA’s advanced detection technology complements existing cold store operations of continual refrigeration, humidity control and storage configurations by utilising this performance-based approach. It is recommended that smoke testing be performed to determine the optimal location for the VESDA detection system. This also allows accurate identification of direction of smoke travel and level of smoke stratification. These tests are usually performed during the commission phase of the cold store, i.e. prior to containing goods. NOTE: The addition of stock will further alter the air dynamics (airflow and air direction) of the cold store facility. This should be acknowledged during the design stage. ROOM PROTECTION VESDA provides early warning smoke detection of freezers/chillers, ante-rooms, loading bays, plant and maintenance rooms via pipework positioned either along the underside of the ceiling or directly through the ceiling using capillary tubes. The first consideration is achieving the best air sampling configuration. There are two (2) alternate approaches: Sampling pipe installed inside the cold store; Sampling pipe installed external to the cold store with capillary tubes entering the cold store. In most cold store facilities, sampling pipework installed within the cold store is the preferred option as fewer ceiling penetrations are required. VESDA 8 3.2.1.
VESDA
®
August, 2001
DESIGN GUIDE
© Vision Fire & Security. All Rights Reserved.
Sampling Point Location
The method of locating the sampling holes is identical in either pipework sampling configuration.
Sampling holes in aspirated smoke detection systems are positioned where conventional detectors
would normally be placed, and according to local prescriptive standards.
International codes and standards recommend both the area of coverage per detector, and also area
coverage at various air change rates. The positioning of the actual detector is usually determined by a
simple grid layout.
Most standards define different grid spacing dependent on certain criteria.
Reference should be made to your relevant standard. Refer to Figure 1.
NOTE:
It is advisable to locate the sampling holes outside the direct airflow path of the Chiller unit.
Figure 1
Grid Layout for Sampling Hole Locations
(X = sampling hole distance – refer to relevant standard)
Chiller
Endcap with
Sampling Hole
Sampling Holes
Airflow
Cold Stores
9
3
.
3
.
®
Cold Stores
DESIGN GUIDE
August, 2001
© Vision Fire & Security. All Rights Reserved.
ALONG UNDERSIDE OF CEILING
Using the above grid layout method, the sampling pipes may be positioned along the underside of the
ceiling. Refer to Figure 2.
Figure 2
Sampling Pipe Along Underside of Ceiling
When installing ceiling mounted pipework, penetrations are drilled through the ceiling insulation panels
and must be fully sealed by either urethane foam (solid/rigid material) or mastic (flexible). The pipe
may also have a seal and/or insulation boot installed to seal the penetrating pipe through the cold
store ceiling. Refer to Figure 3.
Figure 3
Sealing Holes Through Cold Store Ceiling
For ease of installation, a semi flexible pipe material (e.g. PVC, UPVC, HFT, ABS) is used with ceiling
mounted sampling, with particular consideration given to internal temperature fluctuations.
Any mounting clip must allow for pipe movement to accommodate expansion and contraction caused
by temperature fluctuations. In particular, where the pipe is installed in ambient conditions, reference
must be made to the amout of contraction that will occur as the temperature is reduced.
For example, ABS pipe will contract by 0.1% for each 10
°
C(50
°
F) drop in temperature. This is
equivalent to 40mm (1.57”) in a length of 40m (131.2ft) pipe, and will cause the pipe to pull apart if the
Saddle Clip
Sampling
Hole
Ceiling Void
Ceiling Insulation
Ceiling Insulation
Rubber Insulation
Boot
Urea Foam
Mastic
Sealant
Ceiling Void
Icing due to
condensation
Pipe Lagging
Catchment Tray
Penetrations
VESDA
1
0
F)
F)
.
32.
VESDA
®
August, 2001
DESIGN GUIDE
© Vision Fire & Security. All Rights Reserved.
mounting clips constrain the contraction. It may be necessary to locate expansion/contraction offsets
every 10 – 20m (32.8 – 65.6ft) to accommodate the change in pipe length.
NOTE: Pipe connectors should not be positioned adjacent to the mounting clip as this may
also constrain movement.
To reduce the effect of pipework expansion and contraction caused by climatic changes, pipework is
supported by either saddle or offset clips. Refer to Figure 4.
Offset clips are the preferred option in cold store environments. This allows for expansion and
contraction of the pipework during defrosting cycles and other major temperature changes and
removes the need to penetrate the insulation.
Figure 4
Offset Clip
Saddle Clip
NOTE:
Sampling holes should be drilled in the side of the sampling pipe. This reduces the
accumulation of condensation and ice, which could block sampling holes if drilled
underneath the pipe. Refer to Figure 4.
The VESDA detector can be positioned in the ceiling void or external to the protected cold store area.
NOTE: The incidence of condensation accumulating in the sampling pipes and entering the
detector is prevented by ensuring the detector is in an inverted position, i.e. the pipework
enters the detector from underneath.
VESDA detectors can reliably detect smoke samples to a minimum temperature of -20
°
C(-18
°
,
°
°
however, it is recommended that the air sample enters the detector at a temperature of 0
C(32
This is most easily achieved by extending the sampling pipe length outside the 0
°
area and allowing
the ambient air to increase the temperature of the sampled air in the pipe. Copper pipe may be used
for this process due to its heat transfer abilities;
This configuration is sufficient in the majority of cold storage facilities, and pipe runs of 5-10m (16 –
8ft) in the ambient environment is often sufficient.
In cold store conditions where space is limited or pipe runs in ambient temperatures is not possible,
the following options may be employed:
Cold Stores
1
1
100
®
Cold Stores
DESIGN GUIDE
August, 2001
© Vision Fire & Security. All Rights Reserved.
Heat Tracing:
If extending the pipe length is not possible, it may be necessary to trace heat the pipe or capillary
tube. This involves a combination of sampling pipe with heat tracing if the detector is positioned in the
ceiling void. Refer to Figure 5.
Figure 5
Heat Tracing
Heater Box:
•
A heater box may be employed if the length of sampling pipe is not sufficient to allow the air to
warm naturally. The heater is housed within an airtight box and is designed to raise the
temperature of the sampled air before it reaches the VESDA detector. Refer to Figure 6.
Figure 6
Heater Box Arrangement
Ceiling Void
Heat tracing
over pipework
To power supply
Ceiling Insulation
watt dehumidifier heater
Air from Cold Store
Heated Air
To power supply
VESDA
1
2
3
.4
.
3.4.1.
3.4.2.
VESDA
®
August, 2001
DESIGN GUIDE
© Vision Fire & Security. All Rights Reserved.
CONDENSATION CONSIDERATIONS
External Condensation
Sampling pipes or capillary tubes that penetrate the insulation layer are inevitably cold as they enter
the ambient air space (ceiling void). As a result, condensation is likely to occur on the outside of the
sampling pipe and may freeze.
Consideration should be given to insulating the pipe or tube for a short length as it exits the cold store
and to move the risk of ‘melt condensation’ (i.e. water) away from the penetration to an area where it
can be tolerated or contained.
A water catchment tray is recommended to capture the melt
condensation. Refer to Figure 3.
Internal Condensation
Condensation may occur inside the sampling pipe if the external environment is cooler than the
VESDA protected area. While unlikely, some cold store applications may present freezing fog which,
if drawn through the sampling pipe, may melt. The occurance of freezing fog is usually present in the
vicinity of doors and chillers during defrost cycles.
Figure 7
Condensation/Water Trap
A typical water trap configuration requires a T-fitting before the pipe enters the inverted detector,
allowing any presence of water to pool at the stop valve. Refer to Figure 7.
The clear section of the sampling pipe allows maintenance personnel to identify and release ay water
accumulation by opening the stop valve.
NOTE:
It is advised that the stop valve should be open no more than 5 seconds to minimise
the occurance of an airflow fault being reported by the detector.
VESDA’s ASPIRE Sampling Pipe Modelling Program should be used to verify the performance of the
system. As cold temperatures cause air to travel at a slower rate, the sample temperature can be set
Water Catchment Tray
Ceiling Void
Clear pipe to show water build-up
T-fitting
Ceiling Insulation
Stop Valve
Cold Stores
1
3
®
Cold Stores
DESIGN GUIDE
August, 2001
© Vision Fire & Security. All Rights Reserved.
to a range of values in the ASPIRE program and response times can then be recorded. It is always
recommended that a smoke test be performed to verify the detection system.
Points to Consider:
•
It is recommended the VESDA system be fully installed and powered up to ensure optimum air
movement through the pipe, and to avoid the incidence of icing. This is performed during the
commissioning stage of the cold storage facility.
•
To minimise heat transfer during installation in existing cold store retrofits, it is recommended that
pipework is blocked at the point that the pipe leaves the protected area into the ceiling void. The
pipework can be unblocked once the VESDA detector is connected.
•
To avoid icing and condensation, sampling holes should be positioned a minimum of 5 m (16.4 ft)
from doorways or chillers (refer to local codes/standards).
NOTE: Temperature and humidity fluctuations may cause condensation to form on the exterior
of the pipe as it enters the ceiling void from the cold store area. Insulating the pipework as it
enters the ceiling void decreases the level of icing that may form on the exterior of the sample
pipe as it exits the freezer. (Refer to Figure 3)
•
Capillary sampling is an alternative method to ceiling pipework sampling. The sampling pipe is
located in the ceiling space and a capillary sampling tube is connected from the pipe through the
ceiling insulation. Air is then directly sampled from the cold store area. Refer to Figure 8.
The capillary sampling hole position should coincide with the grid layout as described in Section 3.2.1.
Figure 8
Capillary Sampling
Capillary sampling can be labour intensive as each sampling point must be drilled through the
insulation skin of the ceiling. Penetrations need to be fully sealed to prevent ‘melt condensation’
seeping into the insulation barrier and causing damage to the panel.
Points to Consider:
••
•
•
Ceiling mounted pipework only requires one pipework penetration through the cold store ceiling.
(Refer to Figure 2)
••
•
•
In comparison, capillary sampling requires a penetration per sampling point. Refer to Figure 8.
Ceiling Void
Ceiling Insulation
VESDA
1
4
3.5.
3.6
All Rights Reserved in accordance with its policy of continuing product and system improvement. Vision products reserves the right to change designs or specifications August, 2001
without obligation and without further notice. VESDA is a registered trademark of Vision Products Pty Ltd. VESDA LaserPLUS, LaserSCANNER, LaserCOMPACT, © Vision Fire & Security. All Rights Reserved.
DESIGN GUIDE VESDA ® www.vesda.com Australia and Asia Vision Fire & Security Blackburn Road Mount Waverley VIC 3149 Australia Ph +61 3 9211 7200 Fax +61 3 9211 7201 Europe and the Middle East Vision Fire & Security Vision House Focus 31 Mark Road Hemel Hempstead Herts HP2 7BW UK Ph +44 1442 242 330 The Americas Vision Fire & Security Pond Park Road Hingham, MA 02043, USA Ph +1 781 740 2223 Toll Free 800 229 4434 Fax +1 781 740 4433 © 2001 Vision Fire & Security VESDAnet, VESDAlink, ASPIRE, AutoLearn, VSM, VConfig and InfoWORKS are trademark of Vision Products Pty Ltd. Cold Stores